Fading grid on green Commercial Building Ventilation and Indoor Environmental Quality
Table 13 Aldehyde emission factors for indoor sources in the new manufactured study house.

  Emission Factor (µg m-2 h-1)
  Cabinetry Materials, Bare Surface Passage Plywood
Compound PB Topa PB Case Hardbd. Face Frm. Door Subfloora

Formaldehyde 92, 82 470 10 330 153 11, 8
Acetaldehyde 38, 40     20 11 19, 10
Pentanal 51, 42     36 8 28, 25
Hexanal 249, 199     260 42 169, 161
2-Furaldehyde 6, 5   72 7    
Heptanal 12, 9     7   4, 3
2-Heptenal 8, 5     9   5, 5
Benzaldehyde 16b     42 3 5b
Octanal 22, 18     28   8, 8
2-Octenal 19, 12     29   12, 11
Nonanal 19, 16     40   21, 22

a Values are presented for duplicate specimens

b Data for one specimen is missing