Ventilation Rates and Technologies
How are CO2 concentrations related to ventilation rates?
Ventilation rates are inferred from carbon dioxide measurements. Occupants generate carbon dioxide, causing
indoor carbon dioxide concentrations to exceed outdoor concentrations. The ventilation rate (rate of outside air
flow into the building) can be estimated if the indoor carbon dioxide source strength and the concentrations of
supply air and room air are known (ventilation is the only significant process for carbon dioxide removal).
Indoor and outdoor CO2 concentrations are measured and the indoor CO2 source strength is
estimated based on the number of occupants in a building and an estimate of their CO2 production.
However, this method is subject to several sources of error which are described in detail elsewhere
(Persily 1997,
Mudarri 1997,
ASTM D 6245-98) and summarized below:
- Carbon dioxide concentrations have often not stabilized when
the measurements are performed, and the use of non-steady-state
values of carbon dioxide concentration in a steady-state mass
balance equation usually leads to overestimation of the ventilation
rate.
- Carbon dioxide concentrations are often measured using instruments,
such as indicator tubes, with large potential errors.
- Concentrations of carbon dioxide in outdoor air vary with location
and time, and significant error may result if assumed outdoor
concentrations are used in calculations.
- The number, weight, activity and diet of the occupants affect
the indoor carbon dioxide generation rate and each of these parameters
can only be estimated.
- Indoor carbon dioxide concentrations may be spatially non-uniform
and measurements at a few locations may not accurately represent
the average concentration in the exhaust air.
- Use of the peak CO2 instead of actual steady state values may
produce erroneous ventilation rate estimates, off by a factor
of 2 at low ventilation rates, and less at higher ventilation
rates (Persily and Dols 1990).
Figure 1. Typical Carbon Dioxide values measured in US Office Buildings, Statistical distributions
of average workday indoor minus outdoor CO2 concentrations (dCO2)
and peak one-hour minus average outdoor workday CO2 concentrations
(dCO2MAX) in 41 1994-1996 BASE Study office buildings.
(LBNL-44385)
Figure 2. Adjusted analyses of trend for the relationship between workday average indoor minus
outdoor CO2 concentrations (dCO2) and combined and individual mucous membrane and lower respiratory SBS symptoms
in the 1994-1996 BASE Study office buildings with relative humidity > 20%. Odds ratios and 95% confidence intervals,
sample size (N) and WML test statistical significance of the dose-response trend are shown. The models included
covariates to control for age, gender, smoking status, carpet, thermal exposure, RH, and VOC exposure.
(LBNL-44385)
Adjusted analyses of trend for the relationship between workday average indoor minus
outdoor CO2 concentrations (dCO2) and combined and individual mucous
membrane and lower respiratory SBS symptoms in the 1994-1996 BASE
Study office buildings with relative humidity 20%. Odds ratios and
95% confidence intervals, sample size (N) and WML test statistical
significance of the dose-response trend are shown. The models included
covariates to control for age, gender, smoking status, carpet, thermal
exposure, RH, and VOC exposure. (LBNL-44385)
Previous |
Next |