Ventilation Rates and Technologies
The Measurement of Ventilation Rates
The total ventilation rate, because it includes infiltration through the building envelope as well as outdoor air
flow through the ventilation system, can usually be measured only by tracer gas methods
(Sandberg and Sjoberg, 1983 or
ANSI/ASHRAE, 1997). In buildings without air
recirculation, the mechanically-supplied ventilation rate can also be determined with reasonable accuracy by
measuring total supply or exhaust air flow rates. The choice between supply and exhaust flow rate measurements
should be based on the indoor air pressure relative to that outdoors. Typically, to reduce moisture problems,
the design intent is to underpressurize buildings in cold climates and to overpressurize buildings in warm climates.
In underpressurized buildings, the measurement of exhaust flow gives a good estimate for the total ventilation rate,
and in over-pressurized buildings the measurement of supply flow rate indicates the total ventilation rate. If
return air is mixed with outdoor air and recirculated back to the rooms, the supply flow rate must be multiplied
by the proportion of outdoor air in the supply air stream which is measured by a tracer gas procedure or estimated
from CO2 measurements in the return air, outdoor air, and mixed air. Another measurement method used by
air balance professionals is a traverse of air velocities at the outside air intake louver, often with a rotating
vane anemometer. Wind or low air speeds often make it very difficult to accurately determine ventilation rates
using this method. Recently a few vendors have started to market measurement systems for outside airflow that are
installed just upstream or downstream of the outside air intake louvers.
Techniques for Measuring Ventilation Rates
- Blower door
- Tracer gas
Tracer gases can be used to measure the ventilation rate in buildings. The gases used are odorless, nontoxic
and typically used at concentrations in the range of parts per billion (ppb) to part per million (ppm). Some
typical tracers that are used include:
Sulfur Hexafluoride (SF6) , Perfluorocarbons and Carbon Dioxide (CO2).
The tracer gases can be injected continuously or in a single burst
in the supply air duct or in the ventilated occupied space.
- Others such as flow hoods, and VAV box measurements
Typical ventilation rates
|
Table 1
|
Summary information from the three largest surveys of ventilation rates in U.S. commercial and
institutional buildings. (LBNL-49321)
|
|
|
|
Study
|
No. of Buildings
|
Type of Buildings
|
Operating Condition*
|
Reported Ventilation Rates
|
Mean
(GM)
|
St. Dev.
(GSD)
|
Min
|
Max
|
Units
|
|
|
Turk et al., 1989
|
|
24
|
Offices
|
As found
|
1.6 (1.3)
|
0.9 (1.9)
|
0.3
|
2.7
|
h-1
|
|
3
|
Libraries
|
As found
|
0.6
|
0.4
|
0.3
|
1.0
|
h-1
|
|
5
|
Multi use
|
As found
|
1.4
|
0.5
|
0.6
|
1.9
|
h-1
|
|
6
|
Schools
|
As found
|
1.9
|
0.7
|
0.8
|
3.0
|
h-1
|
|
Lagus Applied Tech., 1995
|
|
17
|
Small Office
|
Min. Vent.
|
1.3 (1.2)
|
0.7 (1.8)
|
0.3
|
2.7
|
h-1
|
|
5
|
Large Office
|
Min. Vent.
|
0.8
|
0.6
|
0.7
|
2.7
|
h-1
|
|
13
|
Retail
|
Min. Vent.
|
2.2 (2.2)
|
1.6 (1.6)
|
0.5
|
7.0
|
h-1
|
|
14
|
Schools
|
Min. Vent.
|
2.4 (2.1)
|
1.6 (1.8)
|
1.2
|
2.9
|
h-1
|
|
Persily, 1989
|
14
|
Offices
|
Yearly avg.
|
0.9 (0.8)
|
0.3 (1.5)
|
0.3
|
1.7
|
h-1
|
|
*
With the ventilation system providing the minimum rate of supply of outside air, a normal condition during
cold weather and also when outside temperatures exceed the indoor temperature.
Previous |
Next |