Fading grid on green Commercial Building Ventilation and Indoor Environmental Quality
Home
Research
Publications
References
Staff
Links
Definitions, Standards & Codes
Measurements
CO2 Concentrations
Indoor Air Pollutants
Occupant Health & SBS
Perceived Air Quality
System Types
Productivity
Building Energy Use
Novel Air Supply Technologies
Air Change Effectiveness

Ventilation Rates and Technologies

The Measurement of Ventilation Rates

The total ventilation rate, because it includes infiltration through the building envelope as well as outdoor air flow through the ventilation system, can usually be measured only by tracer gas methods (Sandberg and Sjoberg, 1983 or ANSI/ASHRAE, 1997). In buildings without air recirculation, the mechanically-supplied ventilation rate can also be determined with reasonable accuracy by measuring total supply or exhaust air flow rates. The choice between supply and exhaust flow rate measurements should be based on the indoor air pressure relative to that outdoors. Typically, to reduce moisture problems, the design intent is to underpressurize buildings in cold climates and to overpressurize buildings in warm climates. In underpressurized buildings, the measurement of exhaust flow gives a good estimate for the total ventilation rate, and in over-pressurized buildings the measurement of supply flow rate indicates the total ventilation rate. If return air is mixed with outdoor air and recirculated back to the rooms, the supply flow rate must be multiplied by the proportion of outdoor air in the supply air stream which is measured by a tracer gas procedure or estimated from CO2 measurements in the return air, outdoor air, and mixed air. Another measurement method used by air balance professionals is a traverse of air velocities at the outside air intake louver, often with a rotating vane anemometer. Wind or low air speeds often make it very difficult to accurately determine ventilation rates using this method. Recently a few vendors have started to market measurement systems for outside airflow that are installed just upstream or downstream of the outside air intake louvers.

Techniques for Measuring Ventilation Rates

  • Blower door
  • Tracer gas
  • Tracer gases can be used to measure the ventilation rate in buildings. The gases used are odorless, nontoxic and typically used at concentrations in the range of parts per billion (ppb) to part per million (ppm). Some typical tracers that are used include:

    Sulfur Hexafluoride (SF6) , Perfluorocarbons and Carbon Dioxide (CO2). The tracer gases can be injected continuously or in a single burst in the supply air duct or in the ventilated occupied space.

  • Others such as flow hoods, and VAV box measurements

Typical ventilation rates

Table 1 Summary information from the three largest surveys of ventilation rates in U.S. commercial and institutional buildings. (LBNL-49321)

Study No. of Buildings Type of Buildings Operating Condition* Reported Ventilation Rates
Mean
(GM)
St. Dev.
(GSD)
Min Max Units

Turk et al., 1989
24 Offices As found 1.6 (1.3) 0.9 (1.9) 0.3 2.7 h-1
3 Libraries As found 0.6 0.4 0.3 1.0 h-1
5 Multi use As found 1.4 0.5 0.6 1.9 h-1
6 Schools As found 1.9 0.7 0.8 3.0 h-1
Lagus Applied Tech., 1995
17 Small Office Min. Vent. 1.3 (1.2) 0.7 (1.8) 0.3 2.7 h-1
5 Large Office Min. Vent. 0.8 0.6 0.7 2.7 h-1
13 Retail Min. Vent. 2.2 (2.2) 1.6 (1.6) 0.5 7.0 h-1
14 Schools Min. Vent. 2.4 (2.1) 1.6 (1.8) 1.2 2.9 h-1
Persily, 1989 14 Offices Yearly avg. 0.9 (0.8) 0.3 (1.5) 0.3 1.7 h-1

* With the ventilation system providing the minimum rate of supply of outside air, a normal condition during cold weather and also when outside temperatures exceed the indoor temperature.

Previous | Next

Centrifugal symbol Home | Research | Publications | References | Staff | Links
Indoor Environment Department | EETD | LBNL | Webmaster | Content Master
Centrifugal symbol