Table 5 |
Results of field measurements of air exchange effectiveness, air diffusion effectiveness, and
normalized local ventilation rate by authors and colleagues. |
|
|
Reference,
Bldg. # |
Building or Space Description |
Test # |
% Outside Air |
Air Exchange Effectiveness |
Air Diffusion Effectiveness |
Normalized Local Age of Air |
|
AEEG |
AEEBL |
Min. - Max. |
|
|
Fisk et al 1988
Bldg #1 |
5th fl. office area, 430 m2, CV, induction units supply at 1 m height at perimeter, small AHUin plenum supplies through
ceiling SD in core, all return & exhaust grills at one end of floor |
- |
constant supply of 100% outside air to induction units |
- |
1.4 |
1.2 |
1.2-1.5 |
|
|
Fisk et al 1988,
Bldg #1 |
6th fl., otherwise same as above |
- |
same as above |
- |
1.3 |
- |
1.1-1.6 |
|
|
Fisk et al 1988,
Bldg. B2 & B3 |
two interconnected office bldgs. served by same VAV AHU, 4400 2, RG |
1
2
3 |
17 (min)
29 (min)
31 (min) |
1.4
1.1
1.2 |
1.1
1.0
0.9 |
-
-
1.0 |
1.0-1.4
0.8-1.3
0.8-1.1 |
|
|
Fisk et al 1988,
Bldg B4 |
Office bldg connected to B2 & B3, 2400 m 2, one VAV AHU, ceiling SD & RG |
1
2
3 |
22 (min)
24 (min)
24 (min) |
1.0
1.3
1.3 |
0.9
1.1
1.0 |
-
-
- |
0.9-1.0
0.9-1.1
0.9-1.1 |
|
|
Fisk et al 1991,
Bldg 3 |
University office bldg, 7200 m2, CV with 15 supply fans, ceiling SD & RG |
3
5 |
min +
min + |
-
- |
-
- |
-
- |
-
- |
|
|
Fisk et al 1991,
Bldg 5 |
Office area of science center, 3600 m2, CV, ceiling & high-wall SD &RG |
3
5
7 |
87 (max)
36 (min)
38 (min) |
1.3
-
- |
1.4
0.9
- |
-
-
1.0,1.6,1.4,1.2 |
0.8-3.6
0.6-1.1
0.7-1.0 |
|
|
Fisk et al 1989,
Bldg 6 |
Office bldg, 4100 m2, two VAV AHU with common return shaft, ceiling SD & RG |
1
2
7 |
23,24 (min)
25,24 (min)
86, 80 (max) |
1.1
1.2
1.1 |
1.2
1.0
1.0 |
1.1,1.0,1.0
1.1,1.1,1.0,1.0
1.5,1.1,1.3,1.1,1.2 |
1.1-1.7
0.6-1.3
0.5-1.8 |
|
|
Fisk et al 1991,
Bldg 7 |
Office bldg, 2000 m2, three VAV AHU, ceiling SD & RG |
1
2
3 |
63,33,71 (max)
61,30,70 (max)
10,13,16 (min) |
-
1.0
- |
1.1
0.8
- |
1.2,1.2
1.0,0.8,1.4,1.0
0.9,0.9,1.1,1.0 |
0.8-2.4
0.3-1.4
- |
|
|
Fisk et al 1991,
Bldg 8 |
Office bldg, 950 m2office area, one VAV AHU, ceiling & high wall SG, ceiling RG, high
infiltration, some supply air vented into return plenum |
1
2
3 |
min +
min +
max + |
-
-
- |
-
-
- |
1.2,1.0,0.8,1.3,1.1
1.2,1.1,1.2,1.1
1.1,1.0,1.0,1.1,1.0 |
-
-
- |
|
|
Abbreviations: Bldg=Building; RG=return grill; SD=supply diffuser; min=minimum; max=maximum; occ=occupant; CV=constant volume;
VAV=variable air volume; AHU=air handling unit.
Footnotes: +not measured. |
|
 |