Ventilation Rates and Technologies
What is Air Change Effectiveness?
The air change effectiveness (ACE), is defined as the age of air
that would occur throughout the room if the air was perfectly mixed,
divided by the average age of air where occupants breathe. The age
of air at a particular location is the average time elapsed since
molecules of air at that location entered the building. Because
the average age of air exiting the room is identical to the age
of air that would occur throughout the room if the indoor air were
perfectly mixed, the ACE is also the exhaust-air age divided by
the average age of air where occupants breathe. In practical terms,
the ACE equals the effective ventilation rate at the breathing zone
divided by the ventilation rate that would occur throughout the
building with perfect mixing and at the same outdoor air supply.
A short-circuiting flow pattern between the air supply diffusers
and return grilles, increases the room-air age and causes ACE to
be less than unity. Perfect mixing results in an ACE of unity. Preferentially
ventilating the breathing zone with outside air will cause the ACE
to be greater than unity.
The age of air or its reciprocal, the effective local ventilation
rate, is typically measured by using the tracer gas stepup technique.
(Sandberg and Sjoberg, 1983 or
ANSI/ASHRAE, 1997)
Typical Values Measured for ACE
- Table 6:
Air Change Effectiveness of Conventional Mixing-Type Air Supply Technologies.
Our research as shown that the conventional ceiling-based air supply
technologies used in most US commercial buildings result in an ACE
close to unity. In other words, there is not much short circuiting
of air between supply diffusers and return grilles. The lowest values
of ACE occur when warm air is supplied at the ceiling and the return
grilles are also at the ceiling, and the ventilation system supplies
100% outside air. In this situation, the ACE can be as low as 0.69.
(LBNL-40292)
How is Ventilation Rate Controlled?
Damper set to control minimum outside air supply. But it is very difficult to measure OA supply. In VAV systems,
the OA supply varies with the total air supply. Field studies indicate that actual minimum ventilation rates are
very different from code.